Shuttle
Reference Manual
Space Shuttle
Orbiter Systems
Water Spray Boilers
|
|
The water spray boiler
system consists of three identical independent water spray boilers,
one for a corresponding auxiliary power unit and hydraulic system.
The boilers are located in the aft fuselage of the orbiter. Each
water spray boiler cools the corresponding power unit lube oil system
and hydraulic system by spraying water onto their lines; the water
then boils off, cooling the lube oil and hydraulic fluid. The water
(steam) that boils off in each water spray boiler exits its own
steam duct, located to the right of the vertical stabilizer.
Each water spray boiler
stores water in a bellows-type storage tank pressurized by gaseous
nitrogen to provide positive water expulsion that feeds the boiler.
The hydraulic fluid passes through the boiler three times, and the
lube oil of the auxiliary power unit passes through the boiler twice
in a set of tubes. The hydraulic fluid tubes are sprayed with water
from three water spray bars, and two water spray bars spray the
power unit lube oil. Separate water feed valves allow independent
control of the hydraulic fluid spray bars and power unit lube oil
spray bars. Redundant electrical controllers provide completely
automatic operation.
The boiler system maintains
auxiliary power unit lube oil temperature at approximately 250º
F and the hydraulic fluid in the range of 210º to 220º
F.
The three auxiliary power
units and hydraulic pumps and water spray boilers are in operation
five minutes before lift-off, operate throughout the launch phase
and are shut down after the first orbital maneuvering system thrust
period. One power unit/hydraulic system and corresponding water
spray boiler are operated briefly one day before deorbit during
a checkout of the orbiter flight control system, which includes
the orbiter aerosurfaces.
One auxiliary power unit
is restarted before the deorbit thrusting maneuver. The two remaining
units are started after the deorbit thrusting maneuver and operate
continuously through entry, landing and landing rollout to provide
hydraulic pressure for positioning the orbiter aerosurfaces during
the atmospheric flight portion of entry; deploying the nose and
main landing gear, main landing gear braking and nose wheel steering;
and positioning the three space shuttle main engines after landing
rollout. The corresponding water spray boilers are also in operation
during this period.
Each water spray boiler
is 45 by 31 inches long by 19 inches wide. Each boiler, including
controller and vent nozzle, weighs 181 pounds. They are mounted
in the orbiter aft fuselage between Xo 1340 and 1400, at Zo 488
minus 15, and at Yo plus 15. Insulation blankets cover each boiler.
The boiler's water capacity is 142 pounds.
The gaseous nitrogen pressure
for each water spray boiler is contained in a corresponding 6-inch
spherical pressure vessel. The pressure vessel contains 0.77 pound
of nitrogen at a nominal pressure of 2,400 psi at 70º F. The
gaseous nitrogen storage system of each water spray boiler is directed
to its corresponding water storage tank. Each storage vessel contains
sufficient nitrogen gas to expel all the water from the tank and
allow for relief valve venting during ascent.
The nitrogen shutoff valve
between the pressure valve and water storage tank of each boiler
permits the pressure to reach the nitrogen regulator and water tank
or isolates the nitrogen supply from the water tank. Each nitrogen
valve is controlled by its respective boiler N2 supply 1,2
or 3 switch on panel R2. The nitrogen shutoff valve, which
is latched open or closed consists of two independent solenoid coils
that permit valve control from either the primary or secondary controller.
A single-stage regulator
is installed between the nitrogen pressure shutoff valve and the
water storage tank. The gaseous nitrogen regulator for each water
spray boiler regulates the high-pressure nitrogen between 24.5 and
26 psig as it flows to the water storage tank.
A relief valve is incorporated
inside each nitrogen regulator to prevent the water storage tank
pressure from exceeding 33.5 psig from heat soakback during operations
or in the event of a failed-open nitrogen regulator. The gaseous
nitrogen relief valve opens between 30 to 33.5 psig.
The water supply for each
boiler is stored in a positive-displacement aluminum tank containing
a welded metal bellows separating the stored water inside the bellows
from the nitrogen expulsion gas.
Non-redundant pressure
and temperature sensors located downstream from the gaseous nitrogen
pressure vessel and on the water tank for each boiler transmit the
pressures and temperatures through the A controller to the systems
management general-purpose computer. The computer computes the pressure,
volume and temperature and transmits the water tank quantity to
panel F8 for each boiler. The APU fuel/H20 qty switch on
panel F8 is positioned to allow the water quantity of each boiler
to be displayed on the APU fuel/H20 qty 1,2 or 3 meter.
Thus, water quantity is available only when the A controller is
powered.
Downstream of the water
storage tank, the feedwater lines to each water boiler split into
two parallel lines: one line goes to the hydraulic fluid flow section
and one to the lube oil section of the auxiliary power unit. A hydraulic-fluid
water feed valve is installed in the water line to the hydraulic
fluid section, and a power unit lube oil water feed valve is installed
in the water line to the lube oil section of the power unit. Each
valve is controlled independently by the boiler controller.
The two boiler controllers
are operated by the respective boiler cntlr pwr/htr 1,2 and
3 switches on panel R2. When the applicable switch is positioned
to A, the A controller for that boiler is powered; if it
is positioned to B, the B controller is powered. The off
position of the applicable switch removes electrical power from
both controllers.
The boiler contlr 1,2
and 3 switches on panel R2 enable (provide the automatic
control functions) the specific controller A or B selected for that
boiler by the boiler contlr pwr/htr 1,2 and 3 switches
on panel R2. When the applicable controller A or B is enabled for
that boiler, a ready signal is transmitted to the corresponding
APU/hyd ready to start talkback indicator (along with other
prerequisites from the auxiliary power unit and hydraulic system)
on panel R2 if the following additional conditions are met: gaseous
nitrogen shutoff valve is open, steam vent nozzle temperature is
greater than 130º F, and hydraulic fluid bypass valve is in
the correct position with regard to the hydraulic fluid temperature.
The core of each water
spray boiler is a stainless steel crimped-tube bundle. The hydraulic
fluid section is divided into three 17-inch-long passes of smooth
tubes (first pass—234 tubes, second pass—224 tubes and
third pass—214 tubes). The lube oil section of the auxiliary
power unit comprises two passes with 103 crimped tubes in its first
pass and 81 smooth tubes in the second pass. The tubes are 0.0125
of an inch in diameter with a wall thickness of 0.010 of an inch.
Crimps located every 0.24 of an inch break up the internal boundary
layer and promote enhanced turbulent heat transfer. Although the
second pass is primarily a low-pressure drop return section, approximately
15 percent of the unit's lube oil heat transfer occurs there.
Three connected spray bars
feed the hydraulic fluid section, while two spray bars feed the
power unit's lube oil section in each boiler.
When the orbiter is in
the vertical position on the launch pad, each boiler is loaded with
up to 3.5 pounds of water, which is referred to as pool mode operation.
When each auxiliary power unit/hydraulic system and water spray
boiler is in operation five minutes before lift-off, the power unit
tube bundle and hydraulic tube bundle are immersed in the boiler
water precharge pool mode operation. Liquid level sensors in each
water boiler prevent the water feed valves from pulsing to avoid
water spillage or loss. As the vehicle ascends during launch, the
lube oil system of the auxiliary power unit heats up, eventually
the boiler water precharge boils off, and the boiler goes into the
spray mode. The hydraulic fluid usually does not heat up enough
during ascent to require spray cooling.
The enabled controller
of the operating water spray boiler monitors the hydraulic fluid
and lube oil outlet temperature from the auxiliary power unit. The
hydraulic fluid outlet temperature controls the hydraulic-fluid
water feed valve, and the power unit's lube oil outlet temperature
controls the lube oil water feed valve. Signals are based on a comparison
of the hydraulic system fluid temperature to its 208º F set
point and of the lube oil of the power unit to its 250º F set
point. When the respective water feed valve opens, instantaneous
flows of 10 pounds per minute maximum through the hydraulic section
and 5 pounds per minute maximum through the lube oil section of
the power unit enter the water boiler through the corresponding
spray bars to begin evaporative cooling of the hydraulic fluid and
auxiliary power unit lube oil. The steam is vented out through the
overboard steam vent.
The separate water feed
valves modulate the water flow to each section of the tube bundle
core in each water spray boiler independently in 200-millisecond
pulses that vary from one pulse every 10 seconds to one pulse every
0.25 of a second.
Because of the unique hydraulic
system fluid flows, control valves are located in the hydraulic
system fluid line section of each water spray boiler. Normally,
hydraulic system fluid flows at up to 21 gallons per minute; however,
the hydraulic system experiences one- to two-second flow spikes
at up to 63 gallons per minute. If these spikes were to pass through
the boiler, pressure drop would increase ninefold and the boiler
would limit the flow of the hydraulic system. To prevent this, a
relief function is provided by a spring-loaded poppet valve that
opens when the hydraulic fluid pressure drop exceeds 48 psi and
is capable of flowing 43 gallons per minute at a differential pressure
of 50 psi across the boiler. A temperature controller diverter valve
allows the hydraulic fluid to bypass the boiler when the fluid temperature
decreases to 190º F. At 210º F, the controller commands
the diverter valve to direct the fluid through the boiler. When
the hydraulic fluid cools to 190º F, the controller again commands
the diverter valve to route the fluid around the boiler.
Each water boiler, water
tank and steam vent is equipped with electrical heaters to prevent
freeze-up in orbit. The water tank and boiler electrical heaters
are activated by the corresponding boiler cntlr pwr/htr 1, 2
and 3 switches on panel R2. The A or B position
of each switch selects the A or B heater system and is automatically
controlled by the corresponding A or B controller. The steam vent
heaters are also activated by the boiler cntlr pwr/htr 1, 2
and 3 switches but only if the boiler cntlr 1, 2 or
3 switch on panel R2 is on. The water tank and boiler heaters
are cycled on a 50º F and off at 55º F. The steam vent
heaters are not operated continuously in orbit; they are activated
approximately two hours before auxiliary power unit startup. The
steam vent heaters are cycled on at 150º F and cycled off at
175º F.
When the auxiliary power
unit/hydraulic combination is started for atmospheric entry and
the hydraulic fluid and power unit lube oil flow commences and fluid
temperatures rise, spraying is initiated as required. During the
lower part of entry, when the boiler temperature reaches 188º
F, the water spray boiler returns to the pool mode. The spray bars
begin discharging excess water to fill the boiler. When the water
reaches the liquid level sensors, the spray is turned off so that
the boiler is not overfilled. During entry, because the orbiter's
orientation is different from that of launch, the boiler can hold
up to 14 pounds of water.
Each water spray boiler
transmits data to the systems management summary CRT for display.
Data displayed for each boiler consist of water quantity, gaseous
nitrogen pressure, gaseous nitrogen regulated pressure, bypass valve
status, gaseous nitrogen and water tank temperature, and boiler
temperature.
The boiler system controllers
are powered up at launch minus 4 hours. The boiler water tanks are
pressured at T minus one hour and 10 minutes in preparation for
auxiliary power unit activation. The boiler system controllers activate
heaters on the water tank, boiler and steam vent to ensure that
the water spray boiler is ready to operate for launch.
Auxiliary power unit start
is delayed as long as possible to save fuel. At T minus six minutes,
the pilot begins the power unit prestart sequence—confirming
that the water spray boiler is activated—activates the auxiliary
power unit controllers and depressurizes the main hydraulic pump.
Depressurizing the main pump reduces the starting torque on the
auxiliary power unit. The pilot then opens the auxiliary power unit
fuel tank valves and looks for three APU ready to start gray
talkbacks. At T minus five minutes, the pilot starts the three power
units by setting the APU cntl switches to start/run
and checks the hydraulic power gauges for an indication of approximately
600 to 1,000 psi. Then the pilot pressurizes the main pump and looks
for approximately 3,000 psi on the gauges. All three hydraulic main
pump pressures must be greater than 2,800 psi by T minus four minutes,
or the automatic launch sequencer will abort the launch.
The auxiliary power units
operate during the ascent phase and through the first orbital maneuvering
system thrusting period. At the conclusion of the main engine purge,
dump and stow sequence, the auxiliary power units and water spray
boilers are shut down. The same sequence applies for a delayed OMS-1
thrusting period. If an abort once around is declared, the auxiliary
power units are left running but the hydraulic pumps are depressurized
to reduce power unit fuel consumption. The auxiliary power units
are left running to avoid restarting hot power units for deorbit
and re-entry.
Six hours after lift-off,
the heater gas generator/fuel pump heaters of the auxiliary power
units are activated to operate for the remainder of the orbital
mission. The fuel and water line heaters of the power units are
also activated to prevent the lines from freezing as the units cool
down.
A few hours after lift-off,
the landing gear isolation valves on hydraulic systems 2 and 3 are
opened so that the pumps can circulate hydraulic fluid through the
lines. Because these valves will not open or close unless the pressure
in the line is at least 100 psi, the main hydraulic pump or hydraulic
circulation pump must be active. The hydraulic system 1 landing
gear isolation valve is left closed because of the danger of inadvertently
lowering the landing gear while the vehicle is in orbit.
Two hours after lift-off,
the steam vent heaters of the water spray boilers are turned on
and left on for about 1.5 hours to eliminate all ice from the boiler
steam vents.
While the vehicle is in
orbit, the hydraulic circulation pumps are in the GPC mode (controlled
by the general-purpose computers): automatically activated when
hydraulic line temperatures become too low and automatically deactivated
when the lines warm up sufficiently.
On the day before deorbit,
one auxiliary power unit is started to supply hydraulic pressure
for checkout of the flight control system. (Hydraulic pressure is
needed to move the orbiter aerosurfaces during checkout.) The associated
water spray boiler controller is activated, and landing gear isolation
valves 2 and 3 are closed. Then one auxiliary power unit (selected
by the Mission Control Center) is started. The hydraulic main pump
is set to normal pressure (approximately 3,000 psi), and aerosurface
drive is checked. After about five minutes, the checks are complete
and the power unit is shut down. Normally, the auxiliary power unit
does not run long enough to require water spray boiler operation.
The landing gear isolation valves on hydraulic systems 2 and 3 are
reopened after the auxiliary power unit is shut down.
At 2.5 hours before the
deorbit thrusting period, the steam vent heaters of the water spray
boiler are activated to prepare the boiler systems for operation
during entry. At about the same time, the landing gear isolation
valves on hydraulic systems 2 and 3 are closed, and the circulation
pumps are turned off.
At 45 minutes before deorbit,
the water tanks of the boiler systems are pressurized, the APU controllers
are activated, and the main hydraulic pumps are set at low pressure.
The pilot opens the fuel tank valves of the auxiliary power units
and looks for three gray APU/hyd rdy talkbacks. The pilot
then closes the fuel tank valves. This procedure takes place while
the pilot is in contact with the ground so that flight controllers
can observe the status of the auxiliary power units. Five minutes
before the deorbit thrusting period, one power unit (selected by
Mission Control) is started to ensure that at least one unit will
be operating for entry.
The hydraulic pump is left
in low. This auxiliary power unit operates through the deorbit burn.
At 13 minutes before entry interface (400,000-foot altitude), while
the orbiter is still in free fall, the other two auxiliary power
units are started and all three hydraulic pumps are pressurized
(norm). Two space shuttle main engine hydraulic isolation
valves are cycled open, then closed, to ensure that the engines
are stowed for entry. Two minutes later, if required, the aerosurfaces
are put through an automatic cycle sequence to make sure warm hydraulic
fluid is available in the aerosurface drive units.
After touch down, a hydraulic
load test may be conducted to test the response of the auxiliary
power units and hydraulic pumps under high load (i.e., high flow
demand) conditions. This test cycles the orbiter aerosurfaces with
one hydraulic system at a time in depressed mode (the remaining
two power units and hydraulic pumps have to drive all the aerosurfaces).
This is typically done on the first flight of a new vehicle. The
main engine hydraulic isolation valves are opened again, and the
engines are moved to the transport position. At this point, the
hydraulic systems are no longer needed, and the auxiliary power
units and water spray boilers are shut down.
The contractor for the
water spray boilers is Hamilton Standard Division, United Technologies
Corp., of Windsor Locks, Conn.
|